Specifications
Product Details
LKM 262 Digital Programmable Measuring Transducer
is effected within the measuring transducer itself. The measuring transducer can be programmed by using the universal interface, LKM S1 which is available from RS. An adjusting controller allows immediate minor display corrections.
Zero: -200 to 600°C* depending on thermocouple
Range: 50K
Linearity error: 0.3K depending on the thermocouple
Measurement error: 0.2%
Error of reference junction: +/- 0.5°C
Supply voltage: 15 to 35VDC, 15 to 26VAC reverse polarity protected
Maximum current consumption: 20mA
Output: 0 to 10V programmable
Sensor break: 10V
Short-circuit: voltage value for room temperature
Response time: 0.5s
TC: 100ppm/°C
Operating temperature range: -40 to 85°C
Moisture: 95%
Mounting: 35mm DIN-rail
Housing: Polycarbonate 75x25x53mm
Type of terminals: screw terminals
Clamping range: 0.2 to 2.5mm²
Weight: approx. 60g
Vibration: 5g/10 to 200Hz
Note