Specifications
| Attribute | Value |
|---|---|
| Brand | PR Electronics |
| Input Type | Linear Resistance, RTD, Thermocouple, Voltage |
| Supply Voltage | 8 → 30 V dc |
| Diameter | 23.5 (Width) mm |
| Minimum Temperature Input | -200°C |
| Maximum Temperature Input | 850°C |
| Minimum Operating Temperature | -40°C |
| Maximum Operating Temperature | +85°C |
| Series | 6300 |
| Depth | 104mm |
| Hazardous Area Certification | ATEX |
| Priced to Clear | Yes |
Product Details
6337D 2-Wire HART Transmitter
The 6300 series transmitters are quickly and easily programmable to the specific application. Configuration via a standard PC and user-friendly software, PReset, available as a free download. Parameters for input, output, sensor error detection and process calibration can be configured via PReset within a few minutes.
Features and Benefits
• Galvanic isolation
• Can be installed in Ex zone 0
• Sensor drift detection maintains measuring point reliability
• Flexible input capability, with choice of output modes
• Superior accuracy ensures true, reliable measurements
• Fast response time easily supports safety and cost-critical applications
• High immunity to conducted noise: tested against 10 Vrms in the range 15 Hz–100 MHz
• Continuous check of vital stored data for safety reasons
• Runtime meters provide a valuable history of the process temperature and the ambient temperature around the transmitter
• Very low temperature coefficient ensuring maximum accuracy across changing ambient conditions
What is HART?